Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 2, 2016, 10:32 AM
  • B 1141_B 1140 _060216_033259.mp4

Date
06/02/2016
W/O
574365
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01125
PipeID
P13443
Time
3:32 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3388
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
ALHAMBRA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
WO_574365_TV16044_JUNE2016
Sewer Type
Gravity
Material
BRICK
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
B 1141
Downstream MH
B 1140
Dir. of Survey
Downstream
Length Surveyed
251.7 ft.
Total Length
251.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole B 1141 to B 1140
MH: B 1141MH: B 1140downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 11410 ft. MWM - Water Mark, 25 %of cross sectional area2.1 ft. TFI - Tap Factory Made Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 2"31.5 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"74.6 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"111.3 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"127.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"152.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"251.7 ft. AMH - Downstream Manhole, Survey Ends - B 1140

Observation photos (2)

  • Tap Factory Made Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 2"

    2.1 ft. - Tap Factory Made Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 2"

  • Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"

    111.3 ft. - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"

Observations (11)

DistanceCodeObservation
2.1TFI
111.3TFC
251.7AMHB 1140
0MGOCONNECTION AT MH 3 OCLOCK
152.4TFC
0MWL
74.6TF
0AMHB 1141
127.4TF
31.5TFC
0MWM

Properties (6)

additional_info
SC300388
custom_field_two
4
customer
LACSD
datetime
2016-06-02T03:32:17-07:00
documentation
PROPIPE
is_lateral_inspection
false