Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 31, 2016, 10:12 AM
  • 14 0453_14 0452_31052016_031254.mp4

Date
05/31/2016
W/O
574295
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00570
PipeID
P18541
Time
3:12 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3515
Sewer Name
14 AVENUE "I" TRUNK
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
04
Purpose
Routine Assessment
Project
WO_574295_TV14045_JUNE2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
14 0452
Downstream MH
14 0453
Dir. of Survey
Upstream
Length Surveyed
389.7 ft.
Total Length
389.7 ft.
Structural Index
3
Structural Quick
3M22
Structural Rating
217
O&M Index
2
O&M Quick
3K2N
O&M Rating
331
Overall Index
3
Overall Quick
Overall Rating
548
Pipe schematic from manhole 14 0452 to 14 0453
MH: 14 0452MH: 14 0453upstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 14 04530.5 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK1.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish9.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish61.6 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"77.5 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish109.5 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"111.2 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"161.2 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"164.5 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"211.3 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"215.5 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"263.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"266.3 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"311.1 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"314.1 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"363.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"366.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start366.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"373 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES373 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start376.8 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES387.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start389.7 ft. AMH - Downstream Manhole, Survey Begins - 14 0452389.7 ft. MWL - Water Level, 25 %of cross sectional area389.7 ft. MWM - Water Mark, 40 %of cross sectional area

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    12.9 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    16.7 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    23.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    389.7 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (28)

DistanceCodeObservation
278.5TFC
280.2TF
178.4TF
388.3DAGS
26.3TFC
12.9CL
126.4TFC
389.7MGOCOCKROACHES IN MANHOLE
312.2DSZ
0AMH14 0452
16.7CL
174.2TFC
23.2TF
389.7MGOACTIVE CONNECTION AT MH 3 O'CLOCK
225.2TFA
78.6TFC
228.5TF
123.4TFC
16.7DSZ
389.2MGOACTIVE CONNECTION AT MH 9 O'CLOCK
389.7AMH14 0453
23.5CM
380.1CM
2DAGS
328.1TFC
75.6TFA
0MWL
0MWM

Properties (6)

additional_info
SC305645
custom_field_two
3
customer
LACSD
datetime
2016-05-31T03:12:42-07:00
documentation
PRO PIPE
is_lateral_inspection
false