Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 15, 2016, 07:32 AM
  • 05 1667_05 1666 _061416_123247.mpg

Date
06/15/2016
W/O
563399
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00539
PipeID
P06891
Time
12:32 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3397
Sewer Name
05 WEST TORRANCE TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
32
Purpose
Routine Assessment
Project
WO_563399_TV05132_JUNE2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1667
Downstream MH
05 1666
Dir. of Survey
Downstream
Length Surveyed
268.3 ft.
Total Length
268.3 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
156
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
159
Pipe schematic from manhole 05 1667 to 05 1666
MH: 05 1667MH: 05 1666downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 16670.1 ft. MGO - General Observation - PIPE IS 18"2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start45.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"88.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"144.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"190.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"237.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"247.1 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"262.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish268.3 ft. AMH - Downstream Manhole, Survey Ends - 05 1666

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    247.1 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    262.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observations (13)

DistanceCodeObservation
262.6CM
0MWM
268.3AMH05 1666
144.4TF
88.9TF
190.9TF
45.8TF
247.1TB
0MWL
0.1MGOPIPE IS 18"
2CM
0AMH05 1667
237.8TF

Properties (6)

additional_info
SC300397
custom_field_two
3
customer
LACSD
datetime
2016-06-15T00:32:00-07:00
documentation
PROPIPE
is_lateral_inspection
false