Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 30, 2014, 07:24 AM
  • 22 0231_22 0230_20141229_234349.mp4

Date
12/29/2014
W/O
481935
Weather
Dry
Operator/Surveyor
ERU
Sewer ID
Z00793
PipeID
P16512
Time
11:24 PM
Certificate
123456
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1998
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
35
Purpose
Routine Assessment
Project
WO_481935_TV22017_2014DECEMBER
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Upstream MH
22 0231
Downstream MH
22 0230
Dir. of Survey
Downstream
Length Surveyed
386.6 ft.
Total Length
386.6 ft.
Structural Index
3
Structural Quick
3N00
Structural Rating
225
O&M Index
2
O&M Quick
2N00
O&M Rating
150
Overall Index
3
Overall Quick
Overall Rating
375
Pipe schematic from manhole 22 0231 to 22 0230
MH: 22 0231MH: 22 0230downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 23250 ft. MWM - Water Mark, 40 %of cross sectional area6.1 ft. MGO - General Observation - MAG COATING THROUGHOUT PIPE6.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start14 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"62.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"98.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"110.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"158.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"170.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"206.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"218.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"255.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"267.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"303.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"315.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"351.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"363.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"382.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish386.6 ft. AMH - Downstream Manhole, Survey Ends - 2343

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    6.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
14TF
206.8TFC
303.3TF
158.4TFC
0MWL
255.1TFC
98.2TFC
6.1MGOMAG COATING THROUGHOUT PIPE
351.5TFC
267.5TFA
170.2TFC
0AMH2325
110.5TFC
386.6AMH2343
0MWM
363.8TFA
6.1DAGS
382.4DAGS
315.3TFC
218.9TFC
62.5TFA

Properties (6)

additional_info
SC189563
custom_field_two
4
customer
LACSD
datetime
2014-12-29T23:24:26-08:00
documentation
PROPIPE
is_lateral_inspection
false