Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 23, 2014, 06:03 AM
  • 22 0273_22 0272A_20141222_221308.mp4

Date
12/22/2014
W/O
480783
Weather
Dry
Operator/Surveyor
ERU
Sewer ID
Z00793
PipeID
P16559
Time
10:03 PM
Certificate
123456
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1987-SC189552
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_480783_TV22015_2014DECEMBER
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
15 in.
Upstream MH
22 0273
Downstream MH
22 0272A
Dir. of Survey
Downstream
Length Surveyed
178.6 ft.
Total Length
178.6 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
102
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
102
Pipe schematic from manhole 22 0273 to 22 0272A
MH: 22 0273MH: 22 0272Adownstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22040 ft. MWL - Water Level, 20 %of cross sectional area3.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start39.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6"175.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish178.6 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 8"178.6 ft. AMH - Downstream Manhole, Survey Ends - 2213

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
175.6SAP
39.9TF
178.6TFA
0MWM
3.6SAP
178.6AMH2213
0AMH2204
0MWL

Properties (5)

custom_field_two
CR 3
customer
LACSD
datetime
2014-12-22T22:03:37-08:00
documentation
PROPIPE
is_lateral_inspection
false