Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 27, 2017, 05:17 AM
  • 15 0494_15 0493 _072617_221859.mp4

Date
07/26/2017
W/O
646744
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00629
PipeID
P12419
Time
10:17 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4669
Sewer Name
15 SANTA ANITA OUTFALL TRUNK
City
ROSEMEAD
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
21
Purpose
Routine Assessment
Project
WO_646744_TV15144_JUL2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
15 0494
Downstream MH
15 0493
Dir. of Survey
Downstream
Length Surveyed
369.1 ft.
Total Length
369.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2N11
O&M Rating
147
Overall Index
2
Overall Quick
Overall Rating
147
Pipe schematic from manhole 15 0494 to 15 0493
MH: 15 0494MH: 15 0493downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 04940 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.5 ft. VC - Vermin Cockroach245.6 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 4"369.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0493369.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
369.1AMH15 0493
6.5VC
0AMH15 0494
2DAGS
369.1DAGS
0MWM
245.6TB
0MWL

Properties (6)

additional_info
SC345607
custom_field_two
4
customer
LACSD
datetime
2017-07-26T22:17:40-07:00
documentation
PROPIPE
is_lateral_inspection
false