Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 12, 2017, 12:00 PM
  • G 0113_G0086_9122017_051733.mp4

Date
09/12/2017
W/O
0646199
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01180
PipeID
P02174
Time
5:00 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0641
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Capital Improvement Program Assesment
Project
20170911MDM_JOINT_OUTFALL_G_UNIT_8
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Upstream MH
G 0113
Downstream MH
G 0086
Dir. of Survey
Downstream
Length Surveyed
320.9 ft.
Total Length
320.9 ft.
Structural Index
4
Structural Quick
5541
Structural Rating
31
O&M Index
5
O&M Quick
5141
O&M Rating
9
Overall Index
4
Overall Quick
Overall Rating
40
Pipe schematic from manhole G 0113 to G 0086
MH: G 0113MH: G 0086downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 5:00AM0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. MGO - General Observation - MISSING TILES 95% 9:00 TO 3:00 START2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR LONG & CIRCUM2.3 ft. DSZ - Deposits Settled Other, 50 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start - TILES33 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR47.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR59.5 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - MISSING REBAR73.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO79.5 ft. MGO - General Observation - 3 ROWS TILES 70% IN TACT109.9 ft. MGO - General Observation - 2 ROWS TILES IN TACT190.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open193.3 ft. MGO - General Observation - 70% TILE AREA208.8 ft. MGO - General Observation - MISSING TILES 100%277 ft. MWLS - Water Level, Sag in pipe, 20 %of cross sectional area277 ft. DSZ - Deposits Settled Other, 50 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish - TILES293.5 ft. MGO - General Observation - REMAINING TILES320.5 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active320.5 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG320.5 ft. MGO - General Observation - MISSING TILES 95% 9:00 TO 3:00320.5 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BROKEN MISSING REBAR LONG & CIRCUM320.9 ft. AMH - Downstream Manhole, Survey Ends - 5:40AM

Observation photos (13)

  • General Observation - MISSING TILES 95% 9:00 TO 3:00 START

    2 ft. - General Observation - MISSING TILES 95% 9:00 TO 3:00 START

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR LONG & CIRCUM

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR LONG & CIRCUM

  • Deposits Settled Other,  50 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start - TILES

    2.3 ft. - Deposits Settled Other, 50 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start - TILES

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

    33 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

    47.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - MISSING REBAR

    59.5 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - MISSING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO

    73.6 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO

  • General Observation - 3 ROWS TILES 70% IN TACT

    79.5 ft. - General Observation - 3 ROWS TILES 70% IN TACT

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open

    190.7 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open

  • General Observation - 70% TILE AREA

    193.3 ft. - General Observation - 70% TILE AREA

  • General Observation - MISSING TILES 100%

    208.8 ft. - General Observation - MISSING TILES 100%

  • General Observation - REMAINING TILES

    293.5 ft. - General Observation - REMAINING TILES

Observations (26)

DistanceCodeObservation
59.5SRCMISSING REBAR
0MGOConn. @ Mh, 3 O' Clock. Active
320.5MGOConn. @ Mh, 3 O' Clock. Active
0MGOConn. @ Mh, 9 O' Clock. Active
0MWL
193.3MGO70% TILE AREA
109.9MGO2 ROWS TILES IN TACT
320.9AMH5:40AM
2.3DSZTILES
47.2SRCBROKEN MISSING REBAR
320.5SAMSEVERE AGG
2MGOMISSING TILES 95% 9:00 TO 3:00 START
293.5MGOREMAINING TILES
320.5MGOMISSING TILES 95% 9:00 TO 3:00
2SAMSEVERE AGG AREAS OF MISSING TILES
79.5MGO3 ROWS TILES 70% IN TACT
277MWLS
208.8MGOMISSING TILES 100%
277DSZTILES
2SRCBROKEN MISSING REBAR LONG & CIRCUM
190.7TFOpen
320.5SRCBROKEN MISSING REBAR LONG & CIRCUM
73.6SRC
0AMH5:00AM
0MWM
33SRCBROKEN MISSING REBAR

Properties (6)

custom_field_three
BROKEN MISSING REBAR
custom_field_two
1
customer
LACSD
datetime
2017-09-12T05:00:00-07:00
documentation
MARTIN,MANANES,REVELES.OLIVER 111
is_lateral_inspection
false