Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 30, 2016, 09:41 AM
  • 05 1022_05 1021 _12302016_015242.mp4

Date
12/30/2016
W/O
613357
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00421
PipeID
P06256
Time
1:41 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3953
Sewer Name
05 AVIATION BOULEVARD TRUNK
City
EL SEGUNDO, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
12
Purpose
Routine Assessment
Project
WO_613357_TV05010_JAN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
05 1021
Downstream MH
05 1022
Dir. of Survey
Upstream
Length Surveyed
378.8 ft.
Total Length
378.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2N00
O&M Rating
150
Overall Index
2
Overall Quick
Overall Rating
150
Pipe schematic from manhole 05 1021 to 05 1022
MH: 05 1021MH: 05 1022upstream0 ft. AMH - Upstream Manhole, Survey Ends - 05 10220 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK1.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish376.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start378.8 ft. AMH - Downstream Manhole, Survey Begins - 05 1021378.8 ft. MWL - Water Level, 10 %of cross sectional area378.8 ft. MWM - Water Mark, 25 %of cross sectional area

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
2.2DAGS
378.8AMH05 1022
0AMH05 1021
0MWL
0MWM
378.8MGOCONNECTION AT MH 9 O'CLOCK
377.6DAGS

Properties (6)

additional_info
SC306466
custom_field_two
4
customer
LACSD
datetime
2016-12-30T01:41:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false