Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 27, 2016, 10:52 AM
  • 05 1002_05 1001 _12272016_031932.mp4

Date
12/27/2016
W/O
613357
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00421
PipeID
P06234
Time
2:52 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3949
Sewer Name
05 AVIATION BOULEVARD TRUNK
City
HAWTHORNE, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
16
Purpose
Routine Assessment
Project
WO_613357_TV05010_JAN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1002
Downstream MH
05 1001
Dir. of Survey
Downstream
Length Surveyed
331.4 ft.
Total Length
331.4 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2L11
O&M Rating
131
Overall Index
2
Overall Quick
Overall Rating
134
Pipe schematic from manhole 05 1002 to 05 1001
MH: 05 1002MH: 05 1001downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 10020 ft. MWM - Water Mark, 20 %of cross sectional area0.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start52.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"93.6 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES129.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"206.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"278.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"328.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish331.4 ft. AMH - Downstream Manhole, Survey Ends - 05 1001331.4 ft. VC - Vermin Cockroach

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    93.6 ft. - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
206.9TFC
0MWL
331.4AMH05 1001
0.8DAGS
0AMH05 1002
52.4TFC
278.9TFC
93.6CM
129.5TFC
328.1DAGS
331.4VC
0MWM

Properties (6)

additional_info
SC317697
custom_field_two
4
customer
LACSD
datetime
2016-12-27T02:52:28-08:00
documentation
PRO-PIPE
is_lateral_inspection
false