Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 5, 2017, 07:34 AM
  • 02 1712_02 1711_01042017_233745.mp4

Date
01/04/2017
W/O
613349
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00289
PipeID
P18875
Time
11:34 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4050
Sewer Name
02 MONTEREY PARK EXTENSION TRUNK
City
MONTEREY PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
06
Purpose
Routine Assessment
Project
WO_613349_TV02103_JAN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1712
Downstream MH
02 1711
Dir. of Survey
Downstream
Length Surveyed
247.5 ft.
Total Length
247.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2I00
O&M Rating
98
Overall Index
2
Overall Quick
Overall Rating
98
Pipe schematic from manhole 02 1712 to 02 1711
MH: 02 1712MH: 02 1711downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 17120 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start29.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"50.8 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"85.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"107.2 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"108.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"134.5 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"137.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"196.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"199.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"245.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish247.5 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK247.5 ft. AMH - Downstream Manhole, Survey Ends - 02 1711247.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE247.5 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    247.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (19)

DistanceCodeObservation
85.7TFC
2DAGS
196.2TFC
0AMH02 1712
0MGOCOCKROACHES IN MANHOLE
107.2TBA
50.8TBA
137.1TFC
245.9DAGS
0MWM
108.6TFA
29.6TFC
199.5TFA
247.5MGOACTIVE CONNECTION AT MH 9 O'CLOCK
247.5AMH02 1711
0MWL
134.5TBA
247.5MGOCOCKROACHES IN MANHOLE
247.5MGOACTIVE CONNECTION AT MH 3 O'CLOCK

Properties (6)

additional_info
SC306448
custom_field_two
4
customer
LACSD
datetime
2017-01-04T23:34:42-08:00
documentation
PRO PIPE
is_lateral_inspection
false