Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 28, 2016, 11:05 AM
  • 03 0394_03 0393A _12282016_032019.mp4

Date
12/28/2016
W/O
613343
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00371
PipeID
P04969
Time
3:05 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3901
Sewer Name
03 MARINA TRUNK, SECTION 2
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
25
Purpose
Routine Assessment
Project
WO_613343_TV03019_JAN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
03 0393A
Downstream MH
03 0394
Dir. of Survey
Upstream
Length Surveyed
166.8 ft.
Total Length
166.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
322F
O&M Rating
74
Overall Index
2
Overall Quick
Overall Rating
74
Pipe schematic from manhole 03 0393A to 03 0394
MH: 03 0393AMH: 03 0394upstream0 ft. AMH - Upstream Manhole, Survey Ends - 03 03940 ft. OBZ - Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - DEBRIS NOT VISIBLE POSSIBLE 8 FT AWAY FROM MH0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish17.1 ft. OBZ - Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - DEBRIS NOT VISIBLE37.3 ft. OBZ - Obstacles Other, 10 %of cross sectional area, from 04 to 08 o'clock - DEBRIS NOT VISIBLE164.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start166.8 ft. AMH - Downstream Manhole, Survey Begins - 03 0393A166.8 ft. MWM - Water Mark, 15 %of cross sectional area166.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE166.8 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - DEBRIS NOT VISIBLE POSSIBLE 8 FT AWAY FROM MH

    166.8 ft. - Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - DEBRIS NOT VISIBLE POSSIBLE 8 FT AWAY FROM MH

Observations (10)

DistanceCodeObservation
0AMH03 0393A
149.7OBZDEBRIS NOT VISIBLE
166.8AMH03 0394
0MWM
166.8OBZDEBRIS NOT VISIBLE POSSIBLE 8 FT AWAY FROM MH
0MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
166.8DAGS
2.4DAGS
0MWL
129.5OBZDEBRIS NOT VISIBLE

Properties (6)

additional_info
SC305242
custom_field_two
4
customer
LACSD
datetime
2016-12-28T03:05:32-08:00
documentation
PRO PIPE
is_lateral_inspection
false