Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 5, 2016, 07:43 AM
  • 16 0273_16 0272 _10052016_004322.mp4

Date
10/05/2016
W/O
592155
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00652
PipeID
P13315
Time
12:43 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3774
Sewer Name
16 CHAPEL AVENUE TRUNK, SECTION 1
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Routine Assessment
Project
WO_592155_TV16001_SEP2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
16 0273
Downstream MH
16 0272
Dir. of Survey
Downstream
Length Surveyed
199.8 ft.
Total Length
199.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
312A
O&M Rating
23
Overall Index
2
Overall Quick
Overall Rating
23
Pipe schematic from manhole 16 0273 to 16 0272
MH: 16 0273MH: 16 0272downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 02730 ft. MGO - General Observation - ROACHES IN MH0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start10.5 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR, Start50.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"64.4 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS76 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS90.5 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS102.6 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS114 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS126.3 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS137.4 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS153.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"163.7 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS176.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"187.5 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS190 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"199.8 ft. AMH - Downstream Manhole, Survey Ends - 16 0272199.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish199.8 ft. MGO - General Observation - ROACHES IN MH199.8 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR, Finish

Observation photos (12)

  • General Observation - ROACHES IN MH

    0 ft. - General Observation - ROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR, Start

    10.5 ft. - Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR, Start

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    76 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    90.5 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    102.6 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    114 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    126.3 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    153.2 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    163.7 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    187.5 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • General Observation - ROACHES IN MH

    199.8 ft. - General Observation - ROACHES IN MH

Observations (23)

DistanceCodeObservation
114TFDROOTS
163.7TFDROOTS
64.4TFDROOTS
0MWL
153.2TFC
187.5TFDROOTS
199.8AMH16 0272
199.8DAGS
50.5TFC
2DAGS
199.8MGOROACHES IN MH
0AMH16 0273
0MGOROACHES IN MH
0MWM
126.3TFDROOTS
90.5TFDROOTS
137.4TFDROOTS
176.4TFA
10.5RMJ
199.8RMJ
76TFDROOTS
102.6TFDROOTS
190TBA

Properties (6)

additional_info
SC306311
custom_field_two
4
customer
LACSD
datetime
2016-10-05T00:43:05-07:00
documentation
PRO PIPE
is_lateral_inspection
false