Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 6, 2016, 08:19 AM
  • 16 0258_16 0257 _10062016_012025.mp4

Date
10/06/2016
W/O
592155
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00652
PipeID
P13305
Time
1:19 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3775
Sewer Name
16 CHAPEL AVENUE TRUNK, SECTION 1
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Routine Assessment
Project
WO_592155_TV16001_SEP2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
16 0258
Downstream MH
16 0257
Dir. of Survey
Downstream
Length Surveyed
70.6 ft.
Total Length
70.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 16 0258 to 16 0257
MH: 16 0258MH: 16 0257downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 02580 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start66.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"70.6 ft. AOC - Drop Connection, Survey Ends - 16 025770.6 ft. TFA - Tap Factory Made Active, at 06 o'clock, -, within 8 inches of joint: YES, 18" - DROP CONNECTION70.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
2DAGS
0MWM
70.6AOC16 0257
0AMH16 0258
0MWL
70.6TFADROP CONNECTION
70.6DAGS
66.5TFC

Properties (6)

additional_info
SC306312
custom_field_two
4
customer
LACSD
datetime
2016-10-06T01:19:42-07:00
documentation
PRO PIPE
is_lateral_inspection
false