Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 14, 2016, 06:30 AM
  • H 0477_H 0476_10132016_233234.mp4

Date
10/13/2016
W/O
591875
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00178
PipeID
P21377
Time
11:30 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3782
Sewer Name
H JOINT OUTFALL H - UNIT 5B
City
LA PUENTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
WO_591875_TV15211_SEP2016
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
H 0477
Downstream MH
H 0476
Dir. of Survey
Downstream
Length Surveyed
436.7 ft.
Total Length
436.7 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole H 0477 to H 0476
MH: H 0477MH: H 0476downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 04772 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start8 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"10 ft. MGO - General Observation - MAG COATING 75%69 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"234.7 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"303.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"434.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish436.7 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK436.7 ft. AMH - Downstream Manhole, Survey Ends - H 0476

Observation photos (1)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
436.7MGOACTIVE CONNECTION AT MH 3 O'CLOCK
2SAP
10MGOMAG COATING 75%
69TBA
0MWM
8TBA
434.2SAP
0MWL
0AMHH 0477
303.4TB
234.7TBA
436.7AMHH 0476

Properties (6)

additional_info
SC306319
custom_field_two
2
customer
LACSD
datetime
2016-10-13T23:30:59-07:00
documentation
PRO PIPE
is_lateral_inspection
false