Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 12, 2017, 08:57 AM
  • 05 1544_05 1543_12122017_022136.mp4

Date
12/12/2017
W/O
0673986
Weather
Dry
Operator/Surveyor
MARTIN,MANANES,OLIVER 111
Sewer ID
Z00495
PipeID
P06767
Time
12:57 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0699
Sewer Name
05 NORTH TORRANCE TRUNK
City
TORRANCE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
25
Purpose
Routine Assessment
Project
20171209MDM_NORTH_TORRANCE_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Upstream MH
05 1544
Downstream MH
05 1543
Dir. of Survey
Downstream
Length Surveyed
717.8 ft.
Total Length
717.8 ft.
Structural Index
3
Structural Quick
5333
Structural Rating
30
O&M Index
3
O&M Quick
4224
O&M Rating
16
Overall Index
3
Overall Quick
Overall Rating
46
Pipe schematic from manhole 05 1544 to 05 1543
MH: 05 1544MH: 05 1543downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:25AM1 ft. MGO - General Observation - CRACK IN STACK POURING WATER2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE5.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC19.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG19.7 ft. MGO - General Observation - 18" RCP49.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG64.7 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR67.8 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO, Finish - CIRCUM REBAR145.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE167.2 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: NO - PEELED CONCRETE314.6 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: NO - PEELED CONCRETE365 ft. MWL - Water Level, 50 %of cross sectional area436.5 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start - PEELED CONCRETE & DEBRIE437.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 07 to 10 o'clock, , within 8 inches of joint: YES441.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active443.9 ft. SAP - Surface Aggregate Projecting, from 02 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG453.3 ft. MGO - General Observation - WHITE COATING ON PIPE FROM CONN454.1 ft. MGO - General Observation - WHITE COATING ON PIPE469.3 ft. MWM - Water Mark, 60 %of cross sectional area469.3 ft. MWL - Water Level, 20 %of cross sectional area548.3 ft. MWL - Water Level, 40 %of cross sectional area548.3 ft. MWM - Water Mark, 70 %of cross sectional area593 ft. MWL - Water Level, 20 %of cross sectional area593 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish - PEELED CONCRETE & DEBRIE604.9 ft. SRC - Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: YES - CIRCUM REBAR604.9 ft. SRC - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: YES - CIRCUM REBAR631.8 ft. MWL - Water Level, 10 %of cross sectional area631.8 ft. MWM - Water Mark, 40 %of cross sectional area688.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE692.3 ft. MGO - General Observation - ZOOM 25'717.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERTING PEELING CONCRETE717.3 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active717.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG717.8 ft. AMH - Downstream Manhole, Survey Ends - 3:30AM

Observation photos (15)

  • General Observation - CRACK IN STACK POURING WATER

    1 ft. - General Observation - CRACK IN STACK POURING WATER

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    5.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    19.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - 18" RCP

    19.7 ft. - General Observation - 18" RCP

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

    64.7 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    145.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Deposits Settled Other,  10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start - PEELED CONCRETE & DEBRIE

    436.5 ft. - Deposits Settled Other, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start - PEELED CONCRETE & DEBRIE

  • Deposits Attached Grease, 10 %of cross sectional area, from 07 to 10 o'clock,  , within 8 inches of joint: YES

    437.1 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 07 to 10 o'clock, , within 8 inches of joint: YES

  • Surface Aggregate Projecting, from 02 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

    443.9 ft. - Surface Aggregate Projecting, from 02 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • General Observation - WHITE COATING ON PIPE FROM CONN

    453.3 ft. - General Observation - WHITE COATING ON PIPE FROM CONN

  • General Observation - WHITE COATING ON PIPE

    454.1 ft. - General Observation - WHITE COATING ON PIPE

  • Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    604.9 ft. - Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    604.9 ft. - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    688.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

Observations (37)

DistanceCodeObservation
593MWL
443.9SAPSEVERE AGG
631.8MWL
19.7SAPSEVERE AGG
548.3MWL
5.2SAVSEVERE AGG SPORATIC
717.3SSSBLISTERTING PEELING CONCRETE
365MWL
441.6TBActive
145.2SSSPEELING CONCRETE
604.9SRCCIRCUM REBAR
2SSSBLISTERING PEELING CONCRETE
631.8MWM
548.3MWM
469.3MWM
19.7MGO18" RCP
67.8SRVCIRCUM REBAR
0MWM
717.3MGOConn. @ Mh, 9 O' Clock. Active
604.9SRCCIRCUM REBAR
469.3MWL
49.7SAPSEVERE AGG
1MGOCRACK IN STACK POURING WATER
454.1MGOWHITE COATING ON PIPE
314.6DSZPEELED CONCRETE
0MWL
437.1DAGS
692.3MGOZOOM 25'
167.2DSZPEELED CONCRETE
717.3SAVSEVERE AGG
453.3MGOWHITE COATING ON PIPE FROM CONN
717.8AMH3:30AM
593DSZPEELED CONCRETE & DEBRIE
688.5SSSPEELING CONCRETE
0AMH2:25AM
436.5DSZPEELED CONCRETE & DEBRIE
64.7SRVCIRCUM REBAR

Properties (6)

custom_field_three
CIRCUM REBAR CORRODED
custom_field_two
2
customer
LACSD
datetime
2017-12-12T00:57:36-08:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false