Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 10, 2017, 09:39 AM
  • 18 0365_18 0364 _10052017_023939.mp4

Date
05/10/2017
W/O
630481
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00714
PipeID
P14199
Time
2:39 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4492
Sewer Name
18 WASHINGTON BOULEVARD TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
09
Purpose
Routine Assessment
Project
WO_635481_TV18060_MAY2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0365
Downstream MH
18 0364
Dir. of Survey
Downstream
Length Surveyed
308.1 ft.
Total Length
308.2 ft.
Structural Index
2
Structural Quick
3123
Structural Rating
9
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole 18 0365 to 18 0364
MH: 18 0365MH: 18 0364downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MGO - General Observation - CAPPED LATERAL 9 O'CLOCK @ MH0 ft. AMH - Upstream Manhole, Survey Begins - 18 03650 ft. MGO - General Observation - CAPPED LATERAL 3 O'CLOCK @ MH52.8 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"125.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"148 ft. CM - Crack Multiple, from 12 to 01 o'clock, within 8 inches of joint: YES173.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"175 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES190.4 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES205.4 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES273.8 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"273.8 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 10 o'clock, , within 8 inches of joint: NO308.2 ft. MGO - General Observation - CAPPED LATERAL 9 O'CLOCK @ MH308.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK308.2 ft. AMH - Downstream Manhole, Survey Ends - 18 0364

Observation photos (5)

  • Crack Multiple, from 12 to 01 o'clock, within 8 inches of joint: YES

    148 ft. - Crack Multiple, from 12 to 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    175 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    190.4 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    205.4 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 10 %of cross sectional area, from 08 to 10 o'clock,  , within 8 inches of joint: NO

    273.8 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 10 o'clock, , within 8 inches of joint: NO

Observations (17)

DistanceCodeObservation
0MWL
173.3TFC
0MWM
0MGOCAPPED LATERAL 9 O'CLOCK @ MH
125.8TFC
148CM
308.2MGOCAPPED LATERAL 9 O'CLOCK @ MH
308.2MGOCONNECTION AT MH 3 O'CLOCK
52.8TFA
205.4CL
273.8TFA
308.2AMH18 0364
273.8DAGS
175CL
190.4CL
0AMH18 0365
0MGOCAPPED LATERAL 3 O'CLOCK @ MH

Properties (5)

additional_info
SC345301
custom_field_two
4
customer
LACSD
datetime
2017-05-10T02:39:02-07:00
is_lateral_inspection
false