Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 17, 2017, 08:58 AM
Date
05/17/2017
W/O
635479
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00709
PipeID
P25934
Time
1:58 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4498
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
31
Purpose
Routine Assessment
Project
WO_635479_TV18051_MAY2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 0886
Downstream MH
18 0885A
Dir. of Survey
Downstream
Length Surveyed
421.4 ft.
Total Length
421.4 ft.
Structural Index
4
Structural Quick
5`3`
Structural Rating
1328
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
1328
Pipe schematic from manhole 18 0886 to 18 0885A
MH: 18 0886MH: 18 0885Adownstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 08860 ft. MWL - Water Level, 15 %of cross sectional area6.8 ft. SRV - Surface Reinforcement Visible, from 03 to 05 o'clock, within 8 inches of joint: YES, Start6.8 ft. SAP - Surface Aggregate Projecting, from 07 to 09 o'clock, within 8 inches of joint: YES, Start6.8 ft. SRV - Surface Reinforcement Visible, from 07 to 09 o'clock, within 8 inches of joint: YES, Start6.8 ft. SAP - Surface Aggregate Projecting, from 03 to 05 o'clock, within 8 inches of joint: YES, Start421.4 ft. AMH - Downstream Manhole, Survey Ends - 18 0885A421.4 ft. SAP - Surface Aggregate Projecting, from 03 to 05 o'clock, within 8 inches of joint: YES, Finish421.4 ft. SAP - Surface Aggregate Projecting, from 07 to 09 o'clock, within 8 inches of joint: YES, Finish421.4 ft. SRV - Surface Reinforcement Visible, from 07 to 09 o'clock, within 8 inches of joint: YES, Finish421.4 ft. SRV - Surface Reinforcement Visible, from 03 to 05 o'clock, within 8 inches of joint: YES, Finish421.4 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (4)

  • Surface Reinforcement Visible, from 03 to 05 o'clock, within 8 inches of joint: YES, Start

    6.8 ft. - Surface Reinforcement Visible, from 03 to 05 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 07 to 09 o'clock, within 8 inches of joint: YES, Start

    6.8 ft. - Surface Aggregate Projecting, from 07 to 09 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 07 to 09 o'clock, within 8 inches of joint: YES, Start

    6.8 ft. - Surface Reinforcement Visible, from 07 to 09 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 03 to 05 o'clock, within 8 inches of joint: YES, Start

    6.8 ft. - Surface Aggregate Projecting, from 03 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
6.8SRV
6.8SAP
0MWM
0AMH18 0886
421.4AMH18 0885A
421.4SAP
421.4SAP
6.8SRV
421.4SRV
0MWL
421.4SRV
6.8SAP
421.4MGOCONNECTION AT MH 9 O'CLOCK

Properties (6)

additional_info
SC345307
custom_field_two
2
customer
LACSD
datetime
2017-05-17T01:58:54-07:00
is_lateral_inspection
false
year_laid
39052