Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 14, 2017, 09:42 AM
  • 15 0578_15 0577A _14042017_024311.mp4

Date
04/14/2017
W/O
630147
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00629
PipeID
P25647
Time
2:42 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4467
Sewer Name
15 SANTA ANITA OUTFALL TRUNK
City
ARCADIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Routine Assessment
Project
WO_630147_TV15085_APR2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
15 0578
Downstream MH
15 0577A
Dir. of Survey
Downstream
Length Surveyed
135.1 ft.
Total Length
135.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2E11
O&M Rating
57
Overall Index
2
Overall Quick
Overall Rating
57
Pipe schematic from manhole 15 0578 to 15 0577A
MH: 15 0578MH: 15 0577Adownstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 05780 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start86.2 ft. RFJ - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YES122.4 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES135.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK135.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish135.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0577A

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Settled Other,  5 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES

    122.4 ft. - Deposits Settled Other, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
0MWM
86.2RFJ
0MWL
122.4DSZ
0AMH15 0578
135.1MGOCONNECTION AT MH 9 O'CLOCK
135.1DAGS
0MGOCONNECTION AT MH 3 O'CLOCK
2.5DAGS
135.1AMH15 0577A
0MGOCONNECTION AT MH 9 O'CLOCK

Properties (5)

additional_info
SC345176
custom_field_two
4
customer
LACSD
datetime
2017-04-14T02:42:29-07:00
is_lateral_inspection
false