Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 1, 2017, 08:00 AM
  • Section#1_18 1028_18 1027__812017__G6787.mp4

Date
08/01/2017
W/O
0653438
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00677
PipeID
P14882
Time
1:00 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Heavy Cleaning
Media Label
G6787
Sewer Name
18 LA HABRA HEIGHTS TRUNK, SECTION 1
City
LA HABRA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
20170801MDM_LA_HABRA_HEIGHTS_TRUNK_SECTION_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
7.559999942779541 in.
Upstream MH
18 1028
Downstream MH
18 1027
Dir. of Survey
Downstream
Length Surveyed
346.5 ft.
Total Length
346.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2D00
O&M Rating
48
Overall Index
2
Overall Quick
Overall Rating
48
Pipe schematic from manhole 18 1028 to 18 1027
MH: 18 1028MH: 18 1027downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:05AM7.9 ft. MGO - General Observation - 8"VCP - CIPP117 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN203.9 ft. MGO - General Observation - 8" VCP - CIPP227 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start346.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish346.5 ft. AMH - Downstream Manhole, Survey Ends - 1:35AM

Observation photos (3)

  • General Observation - 8"VCP - CIPP

    7.9 ft. - General Observation - 8"VCP - CIPP

  • General Observation - 8" VCP - CIPP

    203.9 ft. - General Observation - 8" VCP - CIPP

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    227 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
117TBOPEN
7.9MGO8"VCP - CIPP
203.9MGO8" VCP - CIPP
0MWM
0MWL
0AMH1:05AM
346.5AMH1:35AM
346.2DAGS
227DAGS

Properties (7)

custom_field_three
LINER GOOD COND.
custom_field_two
4
customer
LACSD
datetime
2017-08-01T01:00:01-07:00
is_lateral_inspection
false
lining
CIPP
year_laid
20041223