Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 9, 2018, 09:45 AM
  • 05 0815_05 0814 _09112018_014521.mp4

Date
11/09/2018
W/O
735499
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00419
PipeID
P06045
Time
1:45 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6215
Sewer Name
05 ARLINGTON AVENUE EXTENSION TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_735499_TV05345_NOV2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 0815
Downstream MH
05 0814
Dir. of Survey
Downstream
Length Surveyed
338.6 ft.
Total Length
338.6 ft.
Structural Index
2
Structural Quick
312L
Structural Rating
137
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
137
Pipe schematic from manhole 05 0815 to 05 0814
MH: 05 0815MH: 05 0814downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 08150 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"8.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"55.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"58.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"105.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"108.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"155.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"158.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"205.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"208.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"255.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"258 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"305.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"308.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"337 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish337 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH 5% LESS338.6 ft. AMH - Downstream Manhole, Survey Ends - 05 0814338.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
208.5TFC
308.2TF
338.6AMH05 0814
108.5TF
255.7TF
58.5TF
105.8TFC
205.9TF
305.5TF
338.6CM
4CM
337SSS
0AMH05 0815
155.5TF
2SSS
158.4TF
8.5TF
5.9TF
258TF
0MWL
0MWM
337MGOGREASE THROUGHOUT THE REACH 5% LESS
55.8TFC

Properties (6)

additional_info
SC364243
custom_field_two
3
customer
LACSD
datetime
2018-11-09T01:45:17-08:00
documentation
PROPIPE
is_lateral_inspection
false