Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 9, 2018, 05:50 AM
Date
11/08/2018
W/O
735499
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00419
PipeID
P06059
Time
9:50 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6215
Sewer Name
05 ARLINGTON AVENUE EXTENSION TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_735499_TV05345_NOV2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 0829
Downstream MH
05 0828
Dir. of Survey
Downstream
Length Surveyed
293.7 ft.
Total Length
293.7 ft.
Structural Index
2
Structural Quick
312K
Structural Rating
119
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
119
Pipe schematic from manhole 05 0829 to 05 0828
MH: 05 0829MH: 05 0828downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 08290 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"10.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"62.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"64.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"119.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"121.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"173.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"176.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"234 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"236.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"292 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH 5% LESS292 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish293.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK293.7 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK293.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish293.7 ft. AMH - Downstream Manhole, Survey Ends - 05 0828

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
176.2TF
292MGOGREASE THROUGHOUT THE REACH 5% LESS
236.5TF
10.9TF
119.5TF
293.7MGOCONNECTION AT MH 9 O'CLOCK
234TF
0AMH05 0829
0MWM
293.7MGOCONNECTION AT MH 3 O'CLOCK
293.7CM
8TF
2SSS
121.8TF
293.7AMH05 0828
0MWL
6.8CM
173.9TF
64.6TF
62.3TF
292SSS

Properties (6)

additional_info
SC364243
custom_field_two
3
customer
LACSD
datetime
2018-11-08T21:50:59-08:00
documentation
PROPIPE
is_lateral_inspection
false