Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 20, 2019, 05:54 AM
  • 05 1832_05 1831 _03192019_231407.mp4

Date
03/19/2019
W/O
756626
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00492
PipeID
P07054
Time
10:54 PM
Certificate
U-715-000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6484
Sewer Name
05 NARBONNE AVENUE CONNECTION TRUNK
City
LOMITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
36
Purpose
Routine Assessment
Project
WO_756626_TV05075_MAR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
05 1832
Downstream MH
05 1831
Dir. of Survey
Downstream
Length Surveyed
275.7 ft.
Total Length
275.7 ft.
Structural Index
3
Structural Quick
4424
Structural Rating
24
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
26
Pipe schematic from manhole 05 1832 to 05 1831
MH: 05 1832MH: 05 1831downstream0 ft. MGO - General Observation - CONNECTION IN MH 3 OCLOCK0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 18320 ft. MWM - Water Mark, 40 %of cross sectional area6.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"13.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES18.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"43.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"47.6 ft. CH2 - Crack Longitudinal Hinge, 2, from 10 to 02 o'clock, within 8 inches of joint: YES52.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"63.2 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES63.3 ft. FM - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES65.5 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES68.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"84.8 ft. CS - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES87.3 ft. FM - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES116.5 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"119.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"126.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"133.5 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES148.9 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES161.1 ft. CS - Crack Spiral, from 12 to 03 o'clock, within 8 inches of joint: YES, Start178 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"181.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"209.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"211.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"258.2 ft. CS - Crack Spiral, from 12 to 03 o'clock, within 8 inches of joint: YES, Finish264.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"266.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"275.7 ft. MGO - General Observation - CONNECTION IN MH 3 OCLOCK275.7 ft. AMH - Downstream Manhole, Survey Ends - 05 1831

Observation photos (9)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    13.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal Hinge, 2, from 10 to 02 o'clock, within 8 inches of joint: YES

    47.6 ft. - Crack Longitudinal Hinge, 2, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES

    63.2 ft. - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

    63.3 ft. - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    65.5 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

    84.8 ft. - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

    87.3 ft. - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    148.9 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 12 to 03 o'clock, within 8 inches of joint: YES, Start

    161.1 ft. - Crack Spiral, from 12 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (31)

DistanceCodeObservation
43.3TF
275.7MGOCONNECTION IN MH 3 OCLOCK
116.5TBA
0MGOCONNECTION IN MH 3 OCLOCK
0MWL
181.5TFC
266.8TFC
68.3TFC
87.3FM
6.8TF
0AMH05 1832
0MWM
63.3FM
52.6TFA
209.2TFC
211.5TF
47.6CH2
126.1TFA
178TF
133.5RFJ
161.1CS
258.2CS
65.5CL
119.7TF
13.6FM
148.9CL
264.3TF
275.7AMH05 1831
84.8CS
63.2RFJ
18.5TFA

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-03-19T22:54:41-07:00
documentation
PROPIPE
is_lateral_inspection
false