Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 12, 2019, 05:52 AM
  • 05 1834_05 1833 _03112019_231408.mp4

Date
03/11/2019
W/O
756626
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00492
PipeID
P07056
Time
10:52 PM
Certificate
U-715-000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6470
Sewer Name
05 NARBONNE AVENUE CONNECTION TRUNK
City
LOMITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
36
Purpose
Routine Assessment
Project
WO_756626_TV05075_MAR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1834
Downstream MH
05 1833
Dir. of Survey
Downstream
Length Surveyed
209.3 ft.
Total Length
209.3 ft.
Structural Index
3
Structural Quick
443B
Structural Rating
69
O&M Index
2
O&M Quick
2G11
O&M Rating
85
Overall Index
2
Overall Quick
Overall Rating
154
Pipe schematic from manhole 05 1834 to 05 1833
MH: 05 1834MH: 05 1833downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 18341 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"13.7 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES25.9 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES30.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"41 ft. CH2 - Crack Longitudinal Hinge, 2, from 08 to 04 o'clock, within 8 inches of joint: YES62.7 ft. CH2 - Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES70.3 ft. RFL - Roots Fine Lateral, at 02 o'clock70.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"81.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"85.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"105.2 ft. CH2 - Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES114.1 ft. CH2 - Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES120.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES122.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"129.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start155.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"202.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish209 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish209.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK209.3 ft. AMH - Downstream Manhole, Survey Ends - 05 1833

Observation photos (10)

  • Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    13.7 ft. - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    25.9 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal Hinge, 2, from 08 to 04 o'clock, within 8 inches of joint: YES

    41 ft. - Crack Longitudinal Hinge, 2, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES

    62.7 ft. - Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Roots Fine Lateral, at 02 o'clock

    70.3 ft. - Roots Fine Lateral, at 02 o'clock

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"

    81.7 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"

  • Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES

    105.2 ft. - Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES

    114.1 ft. - Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    120.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    129.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (24)

DistanceCodeObservation
9TFC
122.2TF
62.7CH2
25.9CL
129.4CM
209.1MGOCONNECTION AT MH 3 O'CLOCK
13.7CM
0MWM
209.3AMH05 1833
30.8TF
209DAGS
0MWL
41CH2
105.2CH2
155.7TFA
202.1CM
70.3RFL
114.1CH2
1DAGS
120.5CM
0AMH05 1834
85.9TB
81.7TFA
70.3TFA

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-03-11T22:52:30-07:00
documentation
PROPIPE
is_lateral_inspection
false