Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 12, 2019, 04:51 AM
  • 05 1836_05 1835 _03112019_222516.mp4

Date
03/11/2019
W/O
756626
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00492
PipeID
P07058
Time
9:51 PM
Certificate
U-715-000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6470
Sewer Name
05 NARBONNE AVENUE CONNECTION TRUNK
City
LOMITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
35
Purpose
Routine Assessment
Project
WO_756626_TV05075_MAR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1836
Downstream MH
05 1835
Dir. of Survey
Downstream
Length Surveyed
195.3 ft.
Total Length
195.3 ft.
Structural Index
3
Structural Quick
413C
Structural Rating
81
O&M Index
2
O&M Quick
2G00
O&M Rating
78
Overall Index
2
Overall Quick
Overall Rating
159
Pipe schematic from manhole 05 1836 to 05 1835
MH: 05 1836MH: 05 1835downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 18360 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start2.9 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES6.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"10.3 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES18.6 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES29.3 ft. FM - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES32.6 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES38.8 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES44.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start46.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"95 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"143.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"147.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish160.1 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES166.2 ft. CS - Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Start179 ft. SRI - Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: YES183.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"193.3 ft. CS - Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish195 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish195.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK195.3 ft. AMH - Downstream Manhole, Survey Ends - 05 1835

Observation photos (8)

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    10.3 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    18.6 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

    29.3 ft. - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    32.6 ft. - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    38.8 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    44.8 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    160.1 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    166.2 ft. - Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (25)

DistanceCodeObservation
193.3CS
32.6CM
10.3CL
1DAGS
46.2TFA
183.2TFC
160.1CL
44.8CM
195DAGS
29.3FM
195.3MGOCONNECTION AT MH 3 O'CLOCK
0MWL
0AMH05 1836
0MWM
2.9CM
0MGOCONNECTION AT MH 3 O'CLOCK
147.3CM
143.5TF
166.2CS
18.6CL
38.8CL
6.4TFC
95TFA
179SRI
195.3AMH05 1835

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-03-11T21:51:09-07:00
documentation
PROPIPE
is_lateral_inspection
false