Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 8, 2018, 07:05 AM
  • 02 0692_02 0691_08052018_002659.mp4

Date
05/08/2018
W/O
701686
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00311
PipeID
P04576
Time
12:05 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5659
Sewer Name
02 WOODRUFF AVENUE TRUNK
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
30
Purpose
Routine Assessment
Project
WO_701686_TV02370_MAY2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
02 0692
Downstream MH
02 0691
Dir. of Survey
Downstream
Length Surveyed
528.9 ft.
Total Length
528.9 ft.
Structural Index
3
Structural Quick
3T2R
Structural Rating
501
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
501
Pipe schematic from manhole 02 0692 to 02 0691
MH: 02 0692MH: 02 0691downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 06920 ft. MGO - General Observation - CONNECTION AT MH 7 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 2 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start65.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start355.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"362.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"371.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"387.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"451.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"500.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"528.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish528.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish528.9 ft. AMH - Downstream Manhole, Survey Ends - 02 0691

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    65.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
65.2SSS
528.9SSS
2.1SAV
0MWM
500.8TFC
0AMH02 0692
528.9SAV
0MGOCONNECTION AT MH 7 O'CLOCK
387.8TFC
451.3TFC
362.9TFC
0MGOCONNECTION AT MH 2 O'CLOCK
0MWL
371.4TFC
528.9AMH02 0691
355.1TFC

Properties (5)

additional_info
SC359315
custom_field_two
3
customer
LACSD
datetime
2018-05-08T00:05:46-07:00
is_lateral_inspection
false