Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 11, 2018, 09:23 AM
  • B 0010_B 0009_11052018_023843.mp4

Date
05/11/2018
W/O
701684
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00072
PipeID
P08520
Time
2:23 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5668
Sewer Name
B JOINT OUTFALL B - UNIT 1A
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
17
Purpose
Routine Assessment
Project
WO_701684_TV30071_MAY2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
144 in.
Width
144 in.
Upstream MH
B 0010
Downstream MH
B 0009
Dir. of Survey
Downstream
Length Surveyed
241.9 ft.
Total Length
241.9 ft.
Structural Index
4
Structural Quick
5I3I
Structural Rating
387
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
391
Pipe schematic from manhole B 0010 to B 0009
MH: B 0010MH: B 0009downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 00100 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 35 %of cross sectional area2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAG COAT232.9 ft. SRP - Surface Reinforcement Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO241.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish241.9 ft. AMH - Downstream Manhole, Survey Ends - B 0009241.9 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO

    232.9 ft. - Surface Reinforcement Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO

Observations (10)

DistanceCodeObservation
0AMHB 0010
232.9SRP
241.9AMHB 0009
2.1SAP
2.1SRV
0MWM
0MWL
2.1MGOMAG COAT
241.8SAP
241.9SRV

Properties (6)

additional_info
SC359325
custom_field_two
2
customer
LACSD
datetime
2018-05-11T02:23:30-07:00
is_lateral_inspection
false
year_laid
36930