Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 22, 2018, 10:41 AM
  • 18 0352_18 0228 _22052018_035823.mp4

Date
05/22/2018
W/O
701670
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00714
PipeID
P14186
Time
3:41 AM
Certificate
U-0817-07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5617
Sewer Name
18 WASHINGTON BOULEVARD TRUNK
City
WHITTIER, CA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
09
Purpose
Routine Assessment
Project
WO_701670_TV18179_MAY2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0352
Downstream MH
18 0228
Dir. of Survey
Downstream
Length Surveyed
150 ft.
Total Length
150 ft.
Structural Index
3
Structural Quick
4336
Structural Rating
36
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
36
Pipe schematic from manhole 18 0352 to 18 0228
MH: 18 0352MH: 18 0228downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 03522.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES15.1 ft. CM - Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES30 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES34.7 ft. FM - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES49.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES51.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"67.7 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES73.1 ft. CM - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES87.8 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES97.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES99.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"101.4 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES116.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES141.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES150 ft. AMH - Downstream Manhole, Survey Ends - 18 0228

Observation photos (12)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

    15.1 ft. - Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    30 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    34.7 ft. - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    49.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    67.7 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

    73.1 ft. - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES

    87.8 ft. - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    97.7 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES

    101.4 ft. - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    116.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    141.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
30CM
2.3CM
51.3TFC
150AMH18 0228
99.5TFC
0MWL
34.7FM
0MGOCONNECTION AT MH 3 OCLOCK
0MWM
15.1CM
87.8FC
49.8FM
116.6CM
101.4FC
73.1CM
141.7FM
67.7CL
97.7CM
0AMH18 0352

Properties (5)

additional_info
SC359172
custom_field_two
3
customer
LACSD
datetime
2018-05-22T03:41:40-07:00
is_lateral_inspection
false