Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 17, 2018, 02:53 PM
  • B 0007_B 0006_17052018_082306.mp4

Date
05/17/2018
W/O
701389
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00072
PipeID
P08517
Time
7:53 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5671
Sewer Name
B JOINT OUTFALL B - UNIT 1A
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
16
Purpose
Routine Assessment
Project
WO_701389_TV30027_MAY2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
144 in.
Width
144 in.
Upstream MH
B 0007
Downstream MH
B 0006
Dir. of Survey
Downstream
Length Surveyed
1306.9 ft.
Total Length
1306.9 ft.
Structural Index
4
Structural Quick
5s3s
Structural Rating
2091
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
2091
Pipe schematic from manhole B 0007 to B 0006
MH: B 0007MH: B 0006downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 00070 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. MGO - General Observation - MAG COAT2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start2.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start138.4 ft. SRP - Surface Reinforcement Projecting, at 12 o'clock, within 8 inches of joint: NO1306.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish1306.9 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish1306.9 ft. AMH - Downstream Manhole, Survey Ends - B 0006

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Projecting, at 12 o'clock, within 8 inches of joint: NO

    138.4 ft. - Surface Reinforcement Projecting, at 12 o'clock, within 8 inches of joint: NO

Observations (10)

DistanceCodeObservation
1306.9SAP
2.1MGOMAG COAT
2.1SAP
1306.9SRV
138.4SRP
0MWM
2.1SRV
0AMHB 0007
1306.9AMHB 0006
0MWL

Properties (6)

additional_info
SC359329
custom_field_two
2
customer
LACSD
datetime
2018-05-17T07:53:09-07:00
is_lateral_inspection
false
year_laid
36930