Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 9, 2018, 07:22 AM
  • 02 1394_02 1393 _09052018_004318.mp4

Date
05/09/2018
W/O
701119
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00349
PipeID
P02965
Time
12:22 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5661
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
WO_701119_TV02220_MAY2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
02 1394
Downstream MH
02 1393
Dir. of Survey
Downstream
Length Surveyed
649.4 ft.
Total Length
649.4 ft.
Structural Index
4
Structural Quick
5X3X
Structural Rating
1006
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
1006
Pipe schematic from manhole 02 1394 to 02 1393
MH: 02 1394MH: 02 1393downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13947.3 ft. MGO - General Observation - MAG COAT15 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start24.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start649.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish649.4 ft. AMH - Downstream Manhole, Survey Ends - 02 1393649.4 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    15 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    24.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWL
649.4SAP
15SAP
649.4AMH02 1393
649.4SRV
0MWM
0AMH02 1394
24.1SRV
7.3MGOMAG COAT

Properties (5)

additional_info
SC359317
custom_field_two
2
customer
LACSD
datetime
2018-05-09T00:22:00-07:00
is_lateral_inspection
false