Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 22, 2018, 06:00 AM
  • 18 0274_18 0273 _21052018_232158.mp4

Date
05/21/2018
W/O
701118
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00702
PipeID
P14102
Time
11:00 PM
Certificate
U-0817-07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5615
Sewer Name
18 SHOEMAKER AVENUE TRUNK
City
NORWALK, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
30
Purpose
Routine Assessment
Project
WO_701118_TV18148_MAY2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0274
Downstream MH
18 0273
Dir. of Survey
Downstream
Length Surveyed
366.5 ft.
Total Length
366.5 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole 18 0274 to 18 0273
MH: 18 0274MH: 18 0273downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02742.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start17.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"20.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"65.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"68.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"116.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"119.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"168.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"171.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"178.4 ft. DSF - Deposits Settled Fine, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start191 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES193.1 ft. DSF - Deposits Settled Fine, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish213.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"216.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"265.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"268.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"317.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"320.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"354.7 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES360.6 ft. DSGV - Deposits Settled Gravel, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES366.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish366.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0273366.5 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK366.5 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK

Observation photos (5)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Settled Fine,  5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    178.4 ft. - Deposits Settled Fine, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    191 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    354.7 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Deposits Settled Gravel,  5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES

    360.6 ft. - Deposits Settled Gravel, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES

Observations (27)

DistanceCodeObservation
213.9TFC
265.5TFC
168.4TFC
171.4TFC
17.1TFC
0MWM
360.6DSGV
354.7FL
366.5SAV
0MWL
317.1TFC
366.5AMH18 0273
0AMH18 0274
68.4TFC
216.8TFC
193.1DSF
366.5MGOCONNECTION AT MH 9 OCLOCK
119.8TF
320.2TFC
2.2SAV
116.8TFC
20.1TFC
191CM
268.5TF
366.5MGOCONNECTION AT MH 3 OCLOCK
65.3TF
178.4DSF

Properties (5)

additional_info
SC359170
custom_field_two
3
customer
LACSD
datetime
2018-05-21T23:00:15-07:00
is_lateral_inspection
false