Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 18, 2018, 09:28 AM
  • 18 0290_18 0289 _18052018_024834.mp4

Date
05/18/2018
W/O
701118
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00702
PipeID
P14119
Time
2:28 AM
Certificate
U-0817-07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5614
Sewer Name
18 SHOEMAKER AVENUE TRUNK
City
NORWALK, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
25
Purpose
Routine Assessment
Project
WO_701118_TV18148_MAY2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0289
Downstream MH
18 0290
Dir. of Survey
Upstream
Length Surveyed
324.2 ft.
Total Length
324.2 ft.
Structural Index
3
Structural Quick
443L
Structural Rating
215
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
215
Pipe schematic from manhole 18 0289 to 18 0290
MH: 18 0289MH: 18 0290upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 02901.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish10.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"13.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"52 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"56.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"58.5 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES103.8 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES105.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"107.5 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES108.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"135.4 ft. FM - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES150.7 ft. CC - Crack Circumferential, from 09 to 04 o'clock, within 8 inches of joint: YES154.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"157.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"206.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"208.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"236.1 ft. FM - Fracture Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES254.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"258.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"266.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES304.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"307.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"322.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start324.2 ft. MWL - Water Level, 15 %of cross sectional area324.2 ft. AMH - Downstream Manhole, Survey Begins - 18 0289324.2 ft. MWM - Water Mark, 45 %of cross sectional area

Observation photos (8)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    57.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

    88.1 ft. - Fracture Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 09 to 04 o'clock, within 8 inches of joint: YES

    173.5 ft. - Crack Circumferential, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    188.8 ft. - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    216.7 ft. - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    220.4 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    265.7 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

Observations (27)

DistanceCodeObservation
220.4FM
69.8TFC
267.7TFC
324.2AMH18 0290
216.7FL
215.6TFC
166.8TFC
2SAV
115.3TFC
322.7SAV
0MWL
272.2TFC
88.1FM
65.8TFC
16.7TFC
0AMH18 0289
57.3FM
173.5CC
188.8FM
0MWM
310.6TFC
265.7FL
218.7TFC
117.7TFC
19.9TFC
170TFC
314.1TFC

Properties (5)

additional_info
SC359169
custom_field_two
3
customer
LACSD
datetime
2018-05-18T02:28:38-07:00
is_lateral_inspection
false