Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 11, 2018, 08:41 AM
  • 21 0363_21 0362 _11042018_014704.mp4

Date
04/11/2018
W/O
696197
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00778
PipeID
P15565
Time
1:41 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5565
Sewer Name
21 NOGALES STREET TRUNK
City
WALNUT
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
35
Purpose
Routine Assessment
Project
WO_696197_TV21095_APR2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
21 0363
Downstream MH
21 0362
Dir. of Survey
Downstream
Length Surveyed
142.6 ft.
Total Length
142.6 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
81
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
81
Pipe schematic from manhole 21 0363 to 21 0362
MH: 21 0363MH: 21 0362downstream0 ft. AMH - Upstream Manhole, Survey Begins - 21 03630 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 10 %of cross sectional area5.5 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start139.7 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish142.6 ft. AMH - Downstream Manhole, Survey Ends - 21 0362142.6 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (1)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    5.5 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
5.5SAV
139.7SAV
0AMH21 0363
142.6AMH21 0362
0MWM
0MGOCOCKROACHES IN MANHOLE
142.6MGOCOCKROACHES IN MANHOLE
0MWL

Properties (5)

additional_info
SC358524
custom_field_two
4
customer
LACSD
datetime
2018-04-11T01:41:46-07:00
is_lateral_inspection
false