Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 11, 2018, 04:56 AM
  • 08 0075_08 0074 _10042018_221818.mp4

Date
04/10/2018
W/O
694025
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00077
Time
9:56 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5527
Sewer Name
08 MAIN STREET TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
WO_694025_TV08116_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0075
Downstream MH
08 0074
Dir. of Survey
Downstream
Length Surveyed
333.6 ft.
Total Length
333.6 ft.
Structural Index
3
Structural Quick
3222
Structural Rating
10
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
16
Pipe schematic from manhole 08 0075 to 08 0074
MH: 08 0075MH: 08 0074downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH0 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 00753.1 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES6 ft. CM - Crack Multiple, from 08 to 09 o'clock, within 8 inches of joint: YES12.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES15.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start55.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"103.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"153.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"171.9 ft. OBM - Obstacles Pipe Material, 10 %of cross sectional area, from 07 to 09 o'clock201.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"235.8 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES241 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES252.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"302.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"329.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish333.5 ft. MGO - General Observation - CAPPED CONNECTION AT 3 O' CLOCK AT MH333.6 ft. AMH - Downstream Manhole, Survey Ends - 08 0074

Observation photos (7)

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    3.1 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 09 o'clock, within 8 inches of joint: YES

    6 ft. - Crack Multiple, from 08 to 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    12.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    15.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Obstacles Pipe Material, 10 %of cross sectional area, from 07 to 09 o'clock

    171.9 ft. - Obstacles Pipe Material, 10 %of cross sectional area, from 07 to 09 o'clock

  • Deposits Settled Other,  5 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES

    235.8 ft. - Deposits Settled Other, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES

  • Deposits Settled Other,  5 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES

    241 ft. - Deposits Settled Other, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
55.4TF
333.5MGOCAPPED CONNECTION AT 3 O' CLOCK AT MH
0MWM
171.9OBM
252.6TF
12.1CL
0MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
329.7CM
6CM
302.8TFC
333.6AMH08 0074
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
0MWL
15.1CM
0AMH08 0075
241DSZ
3.1CL
103.1TFC
235.8DSZ
201.6TF
153.9TFC

Properties (6)

additional_info
SC358734
custom_field_two
3
customer
LACSD
datetime
2018-04-10T21:56:46-07:00
documentation
PROPIPE
is_lateral_inspection
false