Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 11, 2018, 06:11 AM
  • 08 0078_08 0077 _10042018_233656.mp4

Date
04/10/2018
W/O
694025
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00080
Time
11:11 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5527
Sewer Name
08 MAIN STREET TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
WO_694025_TV08116_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0077
Downstream MH
08 0078
Dir. of Survey
Upstream
Length Surveyed
352 ft.
Total Length
352 ft.
Structural Index
3
Structural Quick
3M21
Structural Rating
209
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
209
Pipe schematic from manhole 08 0077 to 08 0078
MH: 08 0077MH: 08 0078upstream0 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0 ft. AMH - Upstream Manhole, Survey Ends - 08 00780.1 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH0.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish65.5 ft. RPZ - Repair Other, within 8 inches of joint: NO, 6" - POSSIBLE REPAIR @ 02 O'CLOCK119.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"170.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"217.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"268.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"322.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"346 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start348.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES352 ft. MWM - Water Mark, 20 %of cross sectional area352 ft. MWL - Water Level, 15 %of cross sectional area352 ft. AMH - Downstream Manhole, Survey Begins - 08 0077

Observation photos (2)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    3.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
351.9MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
181.8TFC
0MWM
29.7TFC
6CM
351.9CM
352MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
0MWL
0AMH08 0077
3.1CL
352AMH08 0078
286.5RPZPOSSIBLE REPAIR @ 02 O'CLOCK
232.5TFC
134.2TFC
83.4TFC

Properties (6)

additional_info
SC358734
custom_field_two
3
customer
LACSD
datetime
2018-04-10T23:11:56-07:00
documentation
PROPIPE
is_lateral_inspection
false