Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 27, 2017, 01:04 PM
  • 05 1780_05 1779_10272017_060845.mp4

Date
10/27/2017
W/O
0670768
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00473
PipeID
P07011
Time
6:04 AM
Certificate
U-115-0622630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0662
Sewer Name
05 LOMITA TRUNK EXTENSION
City
LOMITA
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
32
Purpose
Capital Improvement Program Assesment
Project
10272017VMR_LOMITA_TRUNK_EXTENSION
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
05 1780
Downstream MH
05 1779A
Dir. of Survey
Downstream
Length Surveyed
59.3 ft.
Total Length
59.3 ft.
Structural Index
1
Structural Quick
1300
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
1
Overall Quick
Overall Rating
3
Pipe schematic from manhole 05 1780 to 05 1779A
MH: 05 1780MH: 05 1779Adownstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 06:00 AM0 ft. MWM - Water Mark, 30 %of cross sectional area27 ft. CC - Crack Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES51 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES59.3 ft. CC - Crack Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES

Observations (6)

DistanceCodeObservation
0MWL
27CC
59.3CC
51CC
0AMH06:00 AM
0MWM

Properties (3)

customer
LACSD
datetime
2017-10-27T06:04:22-07:00
is_lateral_inspection
false