Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 30, 2017, 11:37 AM
  • 02 0297_02 0296_6302017_044200.mp4

Date
06/30/2017
W/O
0647471
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00251
PipeID
P02611
Time
4:37 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0582
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
22A
Purpose
Routine Assessment
Project
20170626MDM_DOWNEY_BELLFLOWER_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0297
Downstream MH
02 0296
Dir. of Survey
Downstream
Length Surveyed
155.6 ft.
Total Length
155.6 ft.
Structural Index
2
Structural Quick
322D
Structural Rating
54
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
54
Pipe schematic from manhole 02 0297 to 02 0296
MH: 02 0297MH: 02 0296downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:40AM0 ft. MWL - Water Level, 10 %of cross sectional area2.8 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - HAIRLINE6.8 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H11.3 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT11.3 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL11.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped14.3 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H26.3 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H26.3 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL30.2 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H30.2 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL34.3 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H38.4 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL46.7 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H50.8 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H62.7 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H63.2 ft. MGO - General Observation - WHITE BUILD UP ON PIPE70.8 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - H75.1 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H82.5 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H90.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H103.1 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL115.2 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H127.7 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - S132.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped138.5 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL142.6 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H146.3 ft. FC - Fracture Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES - H150.9 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H150.9 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL155.2 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active155.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active155.6 ft. AMH - Downstream Manhole, Survey Ends - 5:05AM

Observation photos (1)

  • General Observation - WHITE BUILD UP ON PIPE

    63.2 ft. - General Observation - WHITE BUILD UP ON PIPE

Observations (35)

DistanceCodeObservation
75.1FCH
11.3FCSLIGHT
62.7FCH
150.9FCH
38.4FCSL
26.3FCH
142.6FCH
132.2TFCCapped
30.2FCH
63.2MGOWHITE BUILD UP ON PIPE
2.8FCHAIRLINE
146.3FCH
138.5FCSL
82.5FCH
0MWM
34.3FCH
103.1FCSL
155.6AMH5:05AM
11.3FCSL
46.7FCH
50.8FLH
6.8FCH
115.2FCH
155.2MGOConn. @ Mh, 9 O' Clock. Active
127.7FCS
14.3FCH
11.7TFCCapped
70.8FCH
30.2FCSL
90.9FLH
0AMH4:40AM
26.3FCSL
0MWL
155.2MGOConn. @ Mh, 3 O' Clock. Active
150.9FCSL

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2017-06-30T04:37:57-07:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false