Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 30, 2017, 08:58 AM
  • 02 0302_02 0301_6302017_020447.mp4

Date
06/30/2017
W/O
0647471
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00251
PipeID
P02616
Time
1:58 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0581
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
22A
Purpose
Routine Assessment
Project
20170626MDM_DOWNEY_BELLFLOWER_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0301
Downstream MH
02 0302
Dir. of Survey
Upstream
Length Surveyed
174.5 ft.
Total Length
174.5 ft.
Structural Index
2
Structural Quick
322B
Structural Rating
32
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
38
Pipe schematic from manhole 02 0301 to 02 0302
MH: 02 0301MH: 02 0302upstream0 ft. AMH - Upstream Manhole, Survey Ends - 2:20AM0.3 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Capped0.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active5.8 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - H5.8 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H10.3 ft. FC - Fracture Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES - H18 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL42.4 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H47.1 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - H79.2 ft. MGO - General Observation - WHITE BUILD UP ON PIPE79.2 ft. TBC - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped98.4 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H106.7 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H106.7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H118.7 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL131.3 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H155.7 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H156.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped167 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H171.1 ft. FC - Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - HAIRLINE171.1 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT174.5 ft. AMH - Downstream Manhole, Survey Begins - 2:00AM174.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active174.5 ft. MWM - Water Mark, 50 %of cross sectional area174.5 ft. MWL - Water Level, 40 %of cross sectional area

Observation photos (1)

  • General Observation - WHITE BUILD UP ON PIPE

    95.3 ft. - General Observation - WHITE BUILD UP ON PIPE

Observations (25)

DistanceCodeObservation
168.7FCH
3.4FCHAIRLINE
132.1FCH
7.5FCH
95.3MGOWHITE BUILD UP ON PIPE
67.8FCH
18.1TFCCapped
0AMH2:00AM
174.2MGOConn. @ Mh, 9 O' Clock. Capped
164.2FCH
0MGOConn. @ Mh, 9 O' Clock. Active
127.4FCH
55.8FCSL
95.3TBCCapped
0MWM
76.1FCH
18.8FCH
156.5FLSL
3.4FCSLIGHT
67.8FLH
0MWL
174.2MGOConn. @ Mh, 3 O' Clock. Active
43.2FCH
168.7FCH
174.5AMH2:20AM

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2017-06-30T01:58:00-07:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false