Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 28, 2017, 10:51 AM
  • 02 0308_02 0307_6282017_035738.mp4

Date
06/28/2017
W/O
0647471
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00251
PipeID
P02622
Time
3:51 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0578
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
19A
Purpose
Routine Assessment
Project
20170626MDM_DOWNEY_BELLFLOWER_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0308
Downstream MH
02 0307
Dir. of Survey
Downstream
Length Surveyed
181.5 ft.
Total Length
181.5 ft.
Structural Index
2
Structural Quick
3A2F
Structural Rating
108
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
113
Pipe schematic from manhole 02 0308 to 02 0307
MH: 02 0308MH: 02 0307downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 3:55AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area7 ft. FC - Fracture Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES - HAIRLINE7 ft. FC - Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - SLIGHT10.7 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H14.5 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - H22.9 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL23.6 ft. FC - Fracture Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES - H30.8 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H39.6 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL39.6 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL51.2 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H51.2 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H55.1 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H56.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active58.9 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H67 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SL67 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H71.2 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H71.2 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL75.1 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H75.1 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H79.5 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H79.5 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H83.5 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H87.3 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H88.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped90.4 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H94.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H94.7 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H98.9 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H98.9 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H103.3 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL107.1 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H107.1 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL111.5 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H111.5 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL115.3 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H127.8 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H131.7 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL131.7 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - H135.5 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H139.7 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H144.3 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL148 ft. RML - Roots Medium Lateral, from 11 to 03 o'clock, 25 %, within 8 inches of joint: YES148 ft. TFD - Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active-90% ROOTS154.7 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL154.7 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL163.7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H171.4 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL171.4 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H175 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H175 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL179.4 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL181 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active181.5 ft. AMH - Downstream Manhole, Survey Ends - 4:30AM

Observation photos (1)

  • Roots Medium Lateral, from 11 to 03 o'clock, 25 %, within 8 inches of joint: YES

    148 ft. - Roots Medium Lateral, from 11 to 03 o'clock, 25 %, within 8 inches of joint: YES

Observations (58)

DistanceCodeObservation
75.1FCH
98.9FCH
154.7FCSL
0MGOConn. @ Mh, 3 O' Clock. Active
88.4TFCCapped
7FCHAIRLINE
111.5FCH
181MGOConn. @ Mh, 3 O' Clock. Active
175FCH
171.4FCSL
56.8TFActive
181.5AMH4:30AM
135.5FCH
22.9FCSL
115.3FCH
98.9FLH
58.9FLH
87.3FCH
179.4FCSL
175FCSL
39.6FCSL
148RML
131.7FCSL
154.7FCSL
39.6FCSL
67FLSL
144.3FCSL
107.1FLH
71.2FCH
10.7FLH
111.5FCSL
107.1FCSL
14.5FCH
67FCH
51.2FCH
51.2FLH
127.8FCH
139.7FCH
148TFDActive-90% ROOTS
103.3FCSL
94.7FLH
23.6FCH
0AMH3:55AM
55.1FLH
79.5FCH
83.5FLH
90.4FCH
79.5FCH
30.8FCH
94.7FCH
71.2FCSL
163.7FLH
0MWL
75.1FCH
7FCSLIGHT
0MWM
131.7FLH
171.4FLH

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2017-06-28T03:51:32-07:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false