Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 9, 2019, 05:29 AM
  • 05 0761_05 0760 _05082019_225935.mp4

Date
05/08/2019
W/O
761384
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00484
PipeID
P05988
Time
10:29 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6537
Sewer Name
05 MANCHESTER-VERMONT RELIEF TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_761384_TV05350_APR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 0761
Downstream MH
05 0760
Dir. of Survey
Downstream
Length Surveyed
400.5 ft.
Total Length
400.5 ft.
Structural Index
4
Structural Quick
4O00
Structural Rating
312
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
312
Pipe schematic from manhole 05 0761 to 05 0760
MH: 05 0761MH: 05 0760downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 07610 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area6 ft. FM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES10.9 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start397.9 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish400.5 ft. AMH - Downstream Manhole, Survey Ends - 05 0760

Observation photos (2)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    10.9 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0AMH05 0761
0MWM
0MWL
10.9FM
397.9FM
400.5AMH05 0760
6FM

Properties (4)

custom_field_two
3
customer
LACSD
datetime
2019-05-08T22:29:08-07:00
is_lateral_inspection
false