Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 13, 2019, 09:08 AM
  • G 0144_G 0143_02132019_012736.mp4

Date
02/13/2019
W/O
745594
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z01180
PipeID
P01467
Time
1:08 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6272
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_745594_TV01236_JAN2019
Sewer Type
Gravity
Material
RCP-CTL
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
G 0144
Downstream MH
G 0143
Dir. of Survey
Downstream
Length Surveyed
400.7 ft.
Total Length
400.7 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
4
O&M Quick
5121
O&M Rating
7
Overall Index
4
Overall Quick
Overall Rating
11
Pipe schematic from manhole G 0144 to G 0143
MH: G 0144MH: G 0143downstream0 ft. AMH - Upstream Manhole, Survey Begins - G 01440 ft. MWM - Water Mark, 95 %of cross sectional area0 ft. MWL - Water Level, 75 %of cross sectional area3 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: YES, Start3 ft. MB - Missing Brick, from 09 to 03 o'clock, Start400.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: YES, Finish400.7 ft. MB - Missing Brick, from 09 to 03 o'clock, Finish

Observation photos (2)

  • Deposits Attached Grease, 10 %of cross sectional area, from 11 to 01 o'clock,  , within 8 inches of joint: YES, Start

    3 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: YES, Start

  • Missing Brick, from 09 to 03 o'clock, Start

    3 ft. - Missing Brick, from 09 to 03 o'clock, Start

Observations (7)

DistanceCodeObservation
0AMHG 0144
400.7DAGS
0MWM
3DAGS
400.7MB
0MWL
3MB

Properties (4)

custom_field_two
1
customer
LACSD
datetime
2019-02-13T01:08:02-08:00
is_lateral_inspection
false