Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 29, 2017, 04:46 PM
  • H 0407_H 0406_11292017_093250.mp4

Date
11/29/2017
W/O
0673491
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00177
PipeID
P10841
Time
8:46 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7565
Sewer Name
H JOINT OUTFALL H - UNIT 5A
City
WHITTIER
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
33
Purpose
Routine Assessment
Project
20171129SHO_JOINT_OUTFALL_H_UNIT_5A
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Upstream MH
H 0407
Downstream MH
H 0406
Dir. of Survey
Downstream
Length Surveyed
711.1 ft.
Total Length
711.1 ft.
Structural Index
5
Structural Quick
5431
Structural Rating
23
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
23
Pipe schematic from manhole H 0407 to H 0406
MH: H 0407MH: H 0406downstream0 ft. AMH - Upstream Manhole, Survey Begins - 09400 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start364.5 ft. MGO - General Observation - 15% MAG482 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start487.1 ft. MGP - General Photograph - CORRODED REBAR513 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"554.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Finish652.6 ft. SRC - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO706 ft. SMW - Surface Missing Wall, from 09 to 12 o'clock, within 8 inches of joint: NO, Start - SOIL IS VISIBLE706 ft. MGP - General Photograph - MISSING WALL WITH SOIL VISIBLE711.1 ft. SMW - Surface Missing Wall, from 09 to 12 o'clock, within 8 inches of joint: NO, Finish711.1 ft. AMH - Downstream Manhole, Survey Ends - 1050711.1 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish711.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (8)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    9 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

  • General Observation - 15% MAG

    364.5 ft. - General Observation - 15% MAG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start

    482 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start

  • General Photograph - CORRODED REBAR

    487.1 ft. - General Photograph - CORRODED REBAR

  • Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO

    652.6 ft. - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO

  • Surface Missing Wall, from 09 to 12 o'clock, within 8 inches of joint: NO, Start - SOIL IS VISIBLE

    706 ft. - Surface Missing Wall, from 09 to 12 o'clock, within 8 inches of joint: NO, Start - SOIL IS VISIBLE

  • General Photograph - MISSING WALL WITH SOIL VISIBLE

    706 ft. - General Photograph - MISSING WALL WITH SOIL VISIBLE

Observations (17)

DistanceCodeObservation
482SRC
0AMH0940
711.1SMW
9SAP
706SMWSOIL IS VISIBLE
706MGPMISSING WALL WITH SOIL VISIBLE
487.1MGPCORRODED REBAR
0MWM
652.6SRC
0MWL
711.1AMH1050
364.5MGO15% MAG
554.3SRC
711.1SRV
513TFA
711.1SAP
9SRV

Properties (6)

custom_field_three
MISSING WALL W/ SOIL VISIBLE
custom_field_two
1
customer
LACSD
datetime
2017-11-29T08:46:19-08:00
documentation
OBREGON, BRAR, VENDRYES, PARAISO
is_lateral_inspection
false