Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 16, 2017, 05:54 AM
  • 18 0896_18 0895 _20170515_230624.mpg

Date
05/15/2017
W/O
635479
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00709
PipeID
P14747
Time
10:54 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4497
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
WO_635479_TV18051_MAY2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
18 0896
Downstream MH
18 0895
Dir. of Survey
Downstream
Length Surveyed
369.1 ft.
Total Length
369.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 18 0896 to 18 0895
MH: 18 0896MH: 18 0895downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 08960 ft. MWM - Water Mark, 30 %of cross sectional area2.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.6 ft. MGO - General Observation - MAG COAT368.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish369.1 ft. AMH - Downstream Manhole, Survey Ends - 18 0895

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
2.6SAV
368.4SAV
0MWL
369.1AMH18 0895
0AMH18 0896
0MWM
10.6MGOMAG COAT

Properties (5)

additional_info
SC345306
custom_field_two
3
customer
LACSD
datetime
2017-05-15T22:54:01-07:00
is_lateral_inspection
false