Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 6, 2016, 06:40 AM
  • H 0571_H 0570_05052016_234030.mp4

Date
05/05/2016
W/O
568671
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00188
PipeID
P10995
Time
11:40 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3341
Sewer Name
H JOINT OUTFALL H - UNIT 8E
City
BALDWIN PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
19
Purpose
Routine Assessment
Project
WO_568671_TV15173_MAY2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
H 0571
Downstream MH
H 0570
Dir. of Survey
Downstream
Length Surveyed
301.5 ft.
Total Length
301.5 ft.
Structural Index
3
Structural Quick
3222
Structural Rating
10
O&M Index
2
O&M Quick
4131
O&M Rating
17
Overall Index
2
Overall Quick
Overall Rating
27
Pipe schematic from manhole H 0571 to H 0570
MH: H 0571MH: H 0570downstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK.0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - H 05712 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start3.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start29.4 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS29.4 ft. RML - Roots Medium Lateral, from 09 to 11 o'clock, 10 %, within 8 inches of joint: YES85.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"93.5 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS125.8 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS198.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"206.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"294.8 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish298.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish299.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish301.2 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK.301.2 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK.301.5 ft. AMH - Downstream Manhole, Survey Ends - H 0570301.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (8)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    29.4 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Roots Medium Lateral, from 09 to 11 o'clock, 10 %, within 8 inches of joint: YES

    29.4 ft. - Roots Medium Lateral, from 09 to 11 o'clock, 10 %, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    125.8 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • General Observation - COCKROACHES IN MANHOLE

    301.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (22)

DistanceCodeObservation
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK.
3.1SAV
301.5AMHH 0570
0MWM
301.5MGOCOCKROACHES IN MANHOLE
301.2MGOACTIVE CONNECTION AT MH 9 O'CLOCK.
2SSS
299.6DAGS
0MWL
298.4SSS
85.5TFA
198.5TFC
0MGOCOCKROACHES IN MANHOLE
294.8SAV
125.8TFDROOTS
206.7TBA
93.5TFDROOTS
29.4TFDROOTS
29.4RML
0AMHH 0571
2DAGS
301.2MGOACTIVE CONNECTION AT MH 3 O'CLOCK.

Properties (5)

additional_info
SC305618
custom_field_two
3
customer
LACSD
datetime
2016-05-05T23:40:26-07:00
is_lateral_inspection
false