Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 4, 2018, 06:27 AM
  • B 0455_B 0454A _03042018_232811.mp4

Date
04/03/2018
W/O
698202
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00093
PipeID
P08968
Time
11:27 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5517
Sewer Name
B JOINT OUTFALL B - UNIT 5C
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
11
Purpose
Routine Assessment
Project
WO_698202_DISTRICT16_APR2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
B 0455
Downstream MH
B 0454A
Dir. of Survey
Downstream
Length Surveyed
211.3 ft.
Total Length
211.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole B 0455 to B 0454A
MH: B 0455MH: B 0454Adownstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 04552.9 ft. MGO - General Observation - MAG COAT3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start43 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"51.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"99.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"103.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"103.4 ft. RFC - Roots Fine Connection, at 02 o'clock, within 8 inches of joint: NO162.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"166.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"211.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish211.3 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH211.3 ft. AMH - Downstream Manhole, Survey Ends - B 0454A

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
0MWL
211.3SAP
211.3MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
162.6TFC
103.4TF
2.9MGOMAG COAT
0MWM
51.3TF
99.8TFC
43TFC
211.3AMHB 0454A
166.6TF
3SAP
103.4RFC
0AMHB 0455

Properties (6)

additional_info
SC358724
custom_field_two
2
customer
LACSD
datetime
2018-04-03T23:27:30-07:00
documentation
PROPIPE
is_lateral_inspection
false