Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 4, 2018, 05:36 AM
  • B 0459_B 0458 _03042018_224157.mp4

Date
04/03/2018
W/O
698202
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00093
PipeID
P08972
Time
10:36 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5517
Sewer Name
B JOINT OUTFALL B - UNIT 5C
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
11
Purpose
Routine Assessment
Project
WO_698202_DISTRICT16_APR2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
B 0459
Downstream MH
B 0458
Dir. of Survey
Downstream
Length Surveyed
298.7 ft.
Total Length
298.7 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole B 0459 to B 0458
MH: B 0459MH: B 0458downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 04590 ft. MGO - General Observation - SERVICE CONNECTION AT 6 O' CLOCK AT MH2.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9.6 ft. MGO - General Observation - MAG COAT104.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"184.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"187.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"247.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"250.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"284.3 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO298.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish298.7 ft. AMH - Downstream Manhole, Survey Ends - B 0458

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
187.8TFC
0MWL
284.3DSZ
2.7SAP
247.2TF
250.1TFC
298.7SAP
9.6MGOMAG COAT
0MWM
184.5TFC
0AMHB 0459
104.5TF
298.7AMHB 0458
0MGOSERVICE CONNECTION AT 6 O' CLOCK AT MH

Properties (6)

additional_info
SC358724
custom_field_two
2
customer
LACSD
datetime
2018-04-03T22:36:27-07:00
documentation
PROPIPE
is_lateral_inspection
false