Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 4, 2018, 06:39 AM
  • B 0454A_B 0454 _03042018_234011.mp4

Date
04/03/2018
W/O
698202
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00093
PipeID
P08967
Time
11:39 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5517
Sewer Name
B JOINT OUTFALL B - UNIT 5C
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
11
Purpose
Routine Assessment
Project
WO_698202_DISTRICT16_APR2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
B 0454A
Downstream MH
B 0454
Dir. of Survey
Downstream
Length Surveyed
121 ft.
Total Length
121 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole B 0454A to B 0454
MH: B 0454AMH: B 0454downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 0454A0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area2.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.6 ft. MGO - General Observation - MAG COAT7.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"23.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"74.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"92.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"121 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish121 ft. AMH - Downstream Manhole, Survey Ends - B 0454121 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0AMHB 0454A
23.3TFC
121SAV
92.6TFC
0MWL
121AMHB 0454
74.3TFC
0MWM
7.4TFC
2.6SAV
121MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
2.6MGOMAG COAT

Properties (6)

additional_info
SC358724
custom_field_two
3
customer
LACSD
datetime
2018-04-03T23:39:30-07:00
documentation
PROPIPE
is_lateral_inspection
false