Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 13, 2019, 05:14 PM
  • 15 0847_15 0846_6132019_101917.mp4

  • 15 0847_15 0846_6132019_102229.mp4

Date
06/13/2019
W/O
0775913
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00594
PipeID
P21473
Time
10:14 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7999
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 3&2A
City
SIERRA MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Maintenance Related
Project
20190613DF_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_3_2A
Material
Vitrified Clay Pipe
Shape
Circular
Height
9.399999618530273 in.
Upstream MH
15 0847
Downstream MH
15 0846
Dir. of Survey
Downstream
Length Surveyed
174.7 ft.
Total Length
174.7 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 15 0847 to 15 0846
MH: 15 0847MH: 15 0846downstream0 ft. AMH - Upstream Manhole, Survey Begins - 10:17 AM0.1 ft. MWM - Water Mark, 15 %of cross sectional area0.1 ft. MWL - Water Level, 10 %of cross sectional area0.1 ft. MGO - General Observation - ROACHES @ MH8.1 ft. LFW - Lining Failure Wrinkled, from 04 to 05 o'clock, within 8 inches of joint: YES, Start15.3 ft. MGP - General Photograph - SEAM TAPE 9 TO 12 O,CLOCK68 ft. MGP - General Photograph133 ft. MGP - General Photograph172.6 ft. LFW - Lining Failure Wrinkled, from 04 to 05 o'clock, within 8 inches of joint: YES, Finish172.6 ft. MGO - General Observation - Grease Throughout The Reach (5%)173 ft. MGO - General Observation - ROACHES @ MH174.7 ft. MGO - General Observation - Conn. @ Mh, 5 O' Clock. Active174.7 ft. AMH - Downstream Manhole, Survey Ends - 10:42 AM

Observation photos (4)

  • Lining Failure Wrinkled, from 04 to 05 o'clock, within 8 inches of joint: YES, Start

    8.1 ft. - Lining Failure Wrinkled, from 04 to 05 o'clock, within 8 inches of joint: YES, Start

  • General Photograph - SEAM TAPE 9 TO 12 O,CLOCK

    15.3 ft. - General Photograph - SEAM TAPE 9 TO 12 O,CLOCK

  • General Photograph

    68 ft. - General Photograph

  • General Photograph

    133 ft. - General Photograph

Observations (13)

DistanceCodeObservation
174.7MGOConn. @ Mh, 5 O' Clock. Active
172.6LFW
173MGOROACHES @ MH
15.3MGPSEAM TAPE 9 TO 12 O,CLOCK
172.6MGOGrease Throughout The Reach (5%)
68MGP
0AMH10:17 AM
174.7AMH10:42 AM
8.1LFW
133MGP
0.1MWM
0.1MWL
0.1MGOROACHES @ MH

Properties (8)

additional_info
ROOT EVALUATION ONLY
custom_field_two
4
customer
LACSD
datetime
2019-06-13T10:14:47-07:00
documentation
FRANKLIN, CASTILLO, RUVALCABA
is_lateral_inspection
false
lining
CIPP
year_laid
20020918