Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 12, 2019, 04:44 PM
  • H 0711_H 0710_6122019_094839.mp4

Date
06/12/2019
W/O
0772128
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00941
PipeID
P11118
Time
9:44 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1232
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
WHITTIER
Loc. details
Yard
Location Code
Y
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
20190612SHO_JOINT_OUTFALL_H_UNIT_9B
Material
NRCP
Shape
Circular
Height
25 in.
Upstream MH
H 0711
Downstream MH
H 0710
Dir. of Survey
Downstream
Length Surveyed
525.5 ft.
Total Length
525.5 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole H 0711 to H 0710
MH: H 0711MH: H 0710downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 45 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 07119.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start52 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start525.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish525.5 ft. AMH - Downstream Manhole, Survey Ends - MH H 710 DOES NOT EXIST525.5 ft. MGO - General Observation - 5% OR LESS DEBRIS THROUGHOUT525.5 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Water Mark, 50 %of cross sectional area

    0 ft. - Water Mark, 50 %of cross sectional area

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    52 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWM
0MWL
525.5SAV
9.4SAV
0AMHH 0711
525.5AMHMH H 710 DOES NOT EXIST
525.5MGO5% OR LESS DEBRIS THROUGHOUT
52SSS
525.5SSS

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-06-12T09:44:24-07:00
documentation
OBREGON,C ASTILLO, YOUNG
is_lateral_inspection
false