- Date
- 06/13/2019
- W/O
- 0756080
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00057
- PipeID
- P11472
- Time
- 3:50 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H1231
- Sewer Name
- J JOINT OUTFALL J - UNIT 1E
- City
- PALO VERDES
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 47
- Purpose
- Routine Assessment
- Project
- 20190612MDM_JOINT_OUTFALL_J_UNIT_1E
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 27 in.
- Upstream MH
- J 0225
- Downstream MH
- J 0226
- Dir. of Survey
- Upstream
- Length Surveyed
- 200.7 ft.
- Total Length
- 200.7 ft.
- Structural Index
- 3
- Structural Quick
- 3322
- Structural Rating
- 13
- O&M Index
- 3
- O&M Quick
- 3100
- O&M Rating
- 3
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 16
Pipe schematic from manhole J 0225 to J 0226 Observation photos (6)

2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

8 ft. - General Observation - 27" RCP

109.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

150.3 ft. - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

160.6 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG