Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 4, 2018, 09:45 AM
  • Section#2_08 0466_08 0465__942018__I0060.mp4

Date
09/04/2018
W/O
0717855
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00026
PipeID
P00522
Time
2:45 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0060
Sewer Name
08 216TH STREET TRUNK
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20180904MDM_216TH_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
36 in.
Upstream MH
08 0466
Downstream MH
08 0465
Dir. of Survey
Downstream
Length Surveyed
345.7 ft.
Total Length
345.7 ft.
Structural Index
5
Structural Quick
5[4M
Structural Rating
981
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
981
Pipe schematic from manhole 08 0466 to 08 0465
MH: 08 0466MH: 08 0465downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:50AM0 ft. MGO - General Observation - MH CONN OPEN 3:000 ft. MWL - Water Level, 20 %of cross sectional area0 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MISSING RENAR CORRISON BEYOUND REBAR2 ft. MGO - General Observation - MAG COAT 95% START2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR2 ft. MGO - General Observation - MISSING TILES 50% START9.4 ft. MGO - General Observation - MISSING TILES 95% START13.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR36.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN REBAR CORRISON BEYOUND REBAR54.4 ft. MGO - General Observation - 20% TILES IN PLACE69.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRODED REBAR160.9 ft. MGO - General Observation - 2 ROWS TILES IN PLACE217.3 ft. MGO - General Observation - 2 ROWS OF TILES IN PLACE268.5 ft. MGO - General Observation - BROKEN MISSING REBAR345.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - MISSING REBAR CORRISON BEYOUND REBAR345.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BROKEN MISSING REBAR345.2 ft. MGO - General Observation - MAG COAT 95% FINISH345.2 ft. MGO - General Observation - MH CONN ACTIVE 3:00345.2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG345.2 ft. MGO - General Observation - MISSING TILES 95% FINISH345.7 ft. AMH - Downstream Manhole, Survey Ends - 3:25AM

Observation photos (9)

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MISSING RENAR CORRISON BEYOUND REBAR

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MISSING RENAR CORRISON BEYOUND REBAR

  • General Observation - MAG COAT 95% START

    2 ft. - General Observation - MAG COAT 95% START

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR

  • General Observation - MISSING TILES 50% START

    2 ft. - General Observation - MISSING TILES 50% START

  • General Observation - MISSING TILES 95% START

    9.4 ft. - General Observation - MISSING TILES 95% START

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR

    13.6 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN REBAR CORRISON BEYOUND REBAR

    36.8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN REBAR CORRISON BEYOUND REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRODED REBAR

    69.3 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRODED REBAR

  • General Observation - BROKEN MISSING REBAR

    268.5 ft. - General Observation - BROKEN MISSING REBAR

Observations (24)

DistanceCodeObservation
217.3MGO2 ROWS OF TILES IN PLACE
36.8SRCBROKEN REBAR CORRISON BEYOUND REBAR
160.9MGO2 ROWS TILES IN PLACE
2SRCMISSING RENAR CORRISON BEYOUND REBAR
0MWM
345.2SRCMISSING REBAR CORRISON BEYOUND REBAR
2MGOMAG COAT 95% START
345.2SRCBROKEN MISSING REBAR
2SRCBROKEN MISSING REBAR
345.2MGOMAG COAT 95% FINISH
13.6SRCBROKEN MISSING REBAR
54.4MGO20% TILES IN PLACE
345.7AMH3:25AM
0AMH2:50AM
268.5MGOBROKEN MISSING REBAR
69.3SRCCORRODED REBAR
0MGOMH CONN OPEN 3:00
0MWL
345.2MGOMH CONN ACTIVE 3:00
0SAMSEVERE AGG
2MGOMISSING TILES 50% START
345.2SAMSEVERE AGG
9.4MGOMISSING TILES 95% START
345.2MGOMISSING TILES 95% FINISH

Properties (6)

custom_field_three
MISSING REBAR CORRISON BEYOUND REBAR
custom_field_two
1
customer
LACSD
datetime
2018-09-04T02:45:11-07:00
documentation
MARTIN,REVELES,OLIVER 111,YOUNG
is_lateral_inspection
false